Loft conversions
Fire safety
Means of warning and escape
Mains-wired smoke detectors are needed in the hall, landing and
stairs of all storeys.
- There should be at least one detector on each storey, and the
detectors interlinked (so that a detection of any one, triggers all
of them),
- Each must be mounted within 7.5m of the door to any
habitable room, and at least 300mm from walls and light
fittings, and
- They must be either wired to a separate circuit from the
consumer unit, and have a battery back up.
The existing stairway (i.e., the hall at ground floor, the
stairs from ground to the first floor and the first floor landing)
at ground and first floor level should be enclosed within 30-minute
fire resisting walls. The stairway should not be open to any other
room such as a lounge, kitchen, etc.
Any glazing onto the staircase in the house will need to be
upgraded to give a half hour's fire resistance.
The stairway should open either:
- directly to a final exit or
- to a space from which two escape routes are provided, each
leading to final exits and separated from each other by fire
resisting construction and fire doors.
All existing doors to habitable rooms at ground and first floors
opening onto the hall or landing should be replaced with FD20 fire
doors, and any new doors to the hall and landing need to be fire
resisting as well. There is no longer a requirement that
these doors are made self closing.
If you wish to keep existing doors in place because of the
architectural or historical merit, these will need to be upgraded
to give 30 minutes fire resistance. This can be achieved by the
application of special fire resisting paints, papers or varnishes
(intumescents). There are specialist companies who provide the
materials and assessment service for such upgrades. Building
Control will need a detailed specification to ensure that the doors
will give provide the necessary fire resistance.
A new stair within an existing stairway enclosure should be
separated from any new rooms by an FD20 fire door and fire
resisting walls. Alternatively, the new stair may be separated from
the existing storey by a fire door and fire resisting
construction.
As the staircase is now protected by a fire resisting
enclosure, including the doors, there is no longer a requirement
for an escape window to be provided in the converted loft (new 2nd
floor).
Surface spread of flame
Plastered walls and ceilings generally meet this requirement. Any
timber finishes to the ceiling, and to the walls over a certain
amount, will need to be treated with a fire-retardant paint or
varnish (subject to Building Control approval).
Fire resistance
The new floor and any structure supporting it must have a fire
resistance of 30 minutes from underneath. This should extend to the
inside face of the external walls.
The fire resistance of a floor is dependent on the ceiling
beneath, the size and spacing of joists, and the boards over.
- The existing lath and plaster ceiling below may provide the
required fire resistance, provided that it is in good condition and
firmly attached to the laths. If the ceiling is plasterboarded then
12.5mm thick boards are required to give 30 minutes fire
resistance. You may have to provide an additional skim coat or
additional plasterboard to the ceiling.
- Joists to be at a maximum of 600mm centres, and at least 38mm
wide (if the floor falls outside these limits you should consult
Building Control),
- Floor boarding over to be tongue and grooved, or plain edged
boards overlaid with hardboard (to restrict smoke and hot gases
that might penetrate the ceiling).
The first floor over any habitable rooms under the landing
should also have 30 minutes fire resistance. If the existing floor
is plain edged boards, or badly fitting tongue and grooved boards,
this should be overlaid with hardboard.
The separating walls between dwellings should have at least 60
minutes fire resistance. Some older properties do not have
separating walls within the roof space, or may have holes or gaps
in them. These will need to be sealed up to the underside of the
roof covering. You will also need to be careful of any new
structural elements supported on this wall, or passing through it
(if beams, floor joists or purlins pass through the wall, they can
provide a route for smoke, fire and sound to spread from one house
to another). Please contact Building Control for
advice.
External fire spread
Any dormer cheeks (the triangular external wall to the side)
within 1.0m of a boundary to any other property will need to be
either:
- 30 minutes fire resistant with not more than 2.0m² of
combustible material added to the outside surface (e.g. timber or
uPVC cladding), or
- Not more than 1.0m².
There are requirements for thermoplastic rooflights, and for
combustible materials used as roof coverings. For further advice on
this please refer to Building Control.